Chris,

Since the soil pressure is acting on the bottom of the footing, you need to
add the footing thickness to the moment arm.

David Finley



-----Original Message-----
From: Chris Towne <ctowne(--nospam--at)newwave.net>
To: SEAINT List Server <seaint(--nospam--at)seaint.org>
Date: Wednesday, January 13, 1999 9:32 AM
Subject: Concrete Column Footings


>Situation:
>
>I have a 20' concrete column that is only supported by 7'X7'X3' footing.
>
>Question:
>
>  Is it sufficient to use the moments at the bottom of the column for
>finding footing bearing pressure, or do I need to add the footing thickness
>to the moment arm?
>
>Chris Towne, E.I.T.
>ctowne(--nospam--at)newwave.net
>
>
>
>
>