Thanks Allen for your response to my building drift question..  The elastic 
drift (delta s) is as you say the Inelastic Response Displacement (delta M) 
divided by )  0.7R.  The problem I see is that section 1630.10.1 Story Drift 
Limitation says that "story drifts shall be computed using the Maximium 
Inelastic Response Displacement (delta M)".  I am afraid that this will be 
interpreted as drift that the building cladding system will need to be 
designed  for.

Any other thoughts?

Thanks again

Jim Sadler