I am reviewing Limestone attachment(mechanical) details for a building in
the Los Angeles area.The stone modulus of rupture tests came in at 300PSI.
ASTM 568 for Limestone building stone suggests a minimum of 400 PSI for the
MOR.
The UBC does not address the bending strength nor the MOR of the stone, and
the latest masonry code ACI530.1-99 specifically precludes stone veneer
from the chapter covering veneers.
The question would be for the relevance of the ASTM standard,
If the stone and its attachments are designed with adequate safety factors

Opinions requested, TIA

Tarek Mokhtar, SE
Laguna Beach,CA.