Re: FEMA 350 B.U.E.P. Questions

[Subject Prev][Subject Next][Thread Prev][Thread Next]
FEMA 350 is LRFD.

p-sub-t should be p-sub-f.

c is shown in Figure 3-16.

Rick Drake, SE
Fluor Daniel, Aliso Viejo

*************************************





"Bill Allen, S.E." <Bill(--nospam--at)jrma.com> on 11/21/2000 04:20:27 PM

Please respond to seaint(--nospam--at)seaint.org

To:   <seaint(--nospam--at)seaint.org>
cc:   <roh(--nospam--at)eqe.com>

Subject:  FEMA 350 B.U.E.P. Questions


I have a few questions to anyone who has worked through this design
methodology.

Re: Eqn 3-19, p. 3-45

Is F-sub-v from ASD or LRFD? For example, for A-325 bolts, I believe
F-sub-v
is 48 ksi and not 21 ksi. Is this correct, or is it something else
altogether?

Re: Eqn 3-20, p. 3-46

What is p-sub-t? I cannot find this term defined.

Re: Eqn 3-23, p. 3-46

The only place I find the term "c" is in the RBS design methodology, but it
doesn't make sense in this case. Is there another definition somewhere?

TIA,

Bill Allen, S.E. (CA #2607)











-----------------------------------------------------------------------------------------------------
The information transmitted is intended only for the person
or entity to which it is addressed and may contain confidential
and/or privileged material. If you are not the intended recipient 
of this message you are hereby notified that any use, review,
retransmission, dissemination, distribution, reproduction or any
action taken in reliance upon this message is prohibited. If you 
received this in error, please contact the sender and delete the 
material from any computer.  Any views expressed in this message
are those of the individual sender and may not necessarily reflect 
the views of the company.  
-------------------------------------------------------------------------------------------------------