RE: Concrete tank's vertical reinforcement

[Subject Prev][Subject Next][Thread Prev][Thread Next]
PCA's "Circular Concrete Tanks Without Prestressing" offers some helpful
guidance. Restraint at the bottom of the shell causes vertical bending
moment to be induced in the wall as you apply radial (hydrostatic)load
normal to the wall. Vertical bending moments are also induced by temperature
differentials across the thickness of the wall. These can be larger than you
might think. I would definitely get my hands on the PCA reference. It's not
very thick and doesn't cost much. Check PCA's link below.

http://www.portcement.org/info_resources/results.asp?itemid=IS072&intpage=1&;
searchitem=circular




-----Original Message-----
From: Susan Clinter [mailto:susan_clinter(--nospam--at)hotmail.com]
Sent: Thursday, April 26, 2001 2:08 PM
To: seaint(--nospam--at)seaint.org
Subject: Concrete tank's vertical reinforcement


Does any one has any info on design of circular reinforced concrete tank?
As we know, the horizantal reinforcement is determined by hoop tension 
reslted from radial pressure of water.
But What I'd like to verify is the force that determines the bending moment 
and therefore vertical reinforcement in the wall.
I'd take the lateral  pressure of the water-adjusted for seismic slush- and 
use that to determine the max bending moment in the wall.
Your input is greatly appreciated.
Susan Clinter, PE
_________________________________________________________________________
Get Your Private, Free E-mail from MSN Hotmail at http://www.hotmail.com.


* 
*   This email was sent to you via Structural Engineers 
*   Association of Southern California (SEAOSC) server. To 
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you 
*   send to the list is public domain and may be re-posted 
*   without your permission. Make sure you visit our web 
*   site at: http://www.seaint.org 

* 
*   This email was sent to you via Structural Engineers 
*   Association of Southern California (SEAOSC) server. To 
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you 
*   send to the list is public domain and may be re-posted 
*   without your permission. Make sure you visit our web 
*   site at: http://www.seaint.org