Alex,
With given bolting layout all inside the column flanges, right off hand
I
would view the column base connection being pinned and designed for
shear only, even though it might still be able to develope some fixity.
I
checked manually (too poor to own any STADD or SAP program yet),
that the base connection could develope at most 26% of the column or
the pedestal moment capacity considering ideal fixity of the foundation.

I would  discount any fixity with this column base connection. You
might want to discuss this with the EOR since you are representing the
owner.
Chris Tse
Sunnyvale, CA.


* 