James,

Reference: ACI 117 Standard Specifications for Tolerances for Concrete
Construction and Materials, Section 4.5.5 which will direct you to the ASTM
E 1155 (F sub L and F sub F stuff) or to the straightedge method.  ACI 117
is invoked through ACI 301.  Also check out the ACI 117 commentary, it
explains the tolerances much better.

Regards,
Harold O. Sprague

> -----Original Message-----
> From: JCohen [mailto:jccpc(--nospam--at)email.msn.com]
> Sent: Wednesday, May 09, 2001 8:05 PM
> To: seaint(--nospam--at)seaint.org
> Subject: Floor flatness/stair flatness
> 
> Does anyone know what are the flatness and slope/level requirements for
> floors and stairs, specifically, for a private educational facility
> located
> in Pennsylvania? Any assistance pointing me to the appropriate
> codes/provisions would be very appreciated. I am in the process of seeking
> this information from the PADE but outside help is still appreciated.
> 
> Many thanks.
> 
> James Cohen
> James Cohen Consulting, P.C.
> PO Box 130
> Pennington, NJ 08534
> Tel: (609) 730-0510
> Fax: (609) 730-0511
> Website: http://u2.expertpages.com/jccpc
> 

* 
*   This email was sent to you via Structural Engineers 
*   Association of Southern California (SEAOSC) server. To 
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you 
*   send to the list is public domain and may be re-posted 
*   without your permission. Make sure you visit our web 
*   site at: http://www.seaint.org