Re: UBC 97 Table 16-H

[Subject Prev][Subject Next][Thread Prev][Thread Next]
No, 1000 square feet is correct.  The lower bound value for elements and components is 100 s.f. (interpolating between 10 and 100), this remains constant until 1000 s.f., where you switch to primary frame values.
 
Paul Feather
San Diego, CA
----- Original Message -----
Sent: Thursday, June 07, 2001 8:24 AM
Subject: UBC 97 Table 16-H

UBC 97 Table 16-H (p. 2-29)
Last sentence in footnote 2:  "For tributary areas greater than 1,000 square feet, use primary frame values."
 
Is this supposed to say "100 square feet"?
__________________
John P. Riley, PE, SE
Riley Engineering