RE: IBC 2000 Wind Design

[Subject Prev][Subject Next][Thread Prev][Thread Next]
AISC 7-98

	2.3.2 Load Factor Design

	Formula
	3.	1.2D + 1.6Lr + 0.8W
	4.	1.2D + 1.6W + 0.5L + 0.5(Lr or R or S)

	2.4.1 Allowable Stress Design

	3.	D + W + L + (Lr or R or S)

IBC 2000

	Formula
	16-3		1.2D + 1.6(Lr or S or R) + 0.8(W)
	16-4		1.2D + 1.6W + f1L + 0.5(Lr or R or S)
	16-10		D + W + L + (Lr or R or S)

UBC 97

	Formula
	12-3		1.2D + 1.6(Lr or S) + 0.8W
	12-4		1.2D + 1.3W + f1L + 0.5(Lr or S)
	12-11		D + 0.75[L + (Lr or S) + (W or E/1.4)]


I could not find any notations within the listed codes that say these
combinations are only to be applied to multistory buildings, or that they do
not apply to single story buildings.

Brian


-----Original Message-----
From: Dan Goodrich [mailto:dang(--nospam--at)karren.com]
Sent: Friday, October 05, 2001 8:01 AM
To: seaint(--nospam--at)seaint.org
Subject: Re: IBC 2000 Wind Design


I believe this load combination should be applied to members that are
receiving load from more than one level.  I agree with Roger on this
one.  It doesn't make sense to put a roof live load on at the same time
as a 70 mph wind.  A snow load on the other hand should be used.

Dan Goodrich, P.E.

----- Original Message -----
From: "Brian K. Smith" <smithegr(--nospam--at)bellsouth.net>
To: <seaint(--nospam--at)seaint.org>
Sent: Friday, October 05, 2001 7:31 AM
Subject: RE: IBC 2000 Wind Design


> Well aren't you the smart one.  The fact of the matter is that load
> combinations including dead, roof live, and wind under factored load
design
> and allowable stress design are a requirement of the building code(s).
You
> may have the infinite wisdom to actually know which loading mechanism will
> actually occur and will cause maximum loading, but for the rest of us dumb
> ones, we will have to rely on the building codes.
>
> Brian K. Smith, P.E.
>
>
> -----Original Message-----
> From: Roger Turk [mailto:73527.1356(--nospam--at)compuserve.com]
> Sent: Wednesday, October 03, 2001 9:01 PM
> To: seaint(--nospam--at)seaint.org
> Subject: RE: IBC 2000 Wind Design
>
>
> Brian Smith wrote:
>
> . > If you combine your out of plane wind loads with the roof live loads
you
> . > can reduce the two transient loads by 0.75, with no increase in
> allowable
> . > stresses.
>
> Nobody in his/her right mind will be on a roof in anywhere near 70-80 mph
> winds, and even if there had been roofing material on the roof before the
> winds reached 70-80 mph, it isn't there now.
>
> A. Roger Turk, P.E.(Structural)
> Tucson, Arizona
>
> ******* ****** ******* ******** ******* ******* ******* ***
> *   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
> *
> *   This email was sent to you via Structural Engineers
> *   Association of Southern California (SEAOSC) server. To
> *   subscribe (no fee) or UnSubscribe, please go to:
> *
> *   http://www.seaint.org/sealist1.asp
> *
> *   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you
> *   send to the list is public domain and may be re-posted
> *   without your permission. Make sure you visit our web
> *   site at: http://www.seaint.org
> ******* ****** ****** ****** ******* ****** ****** ********
>
>
>
> ******* ****** ******* ******** ******* ******* ******* ***
> *   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
> *
> *   This email was sent to you via Structural Engineers
> *   Association of Southern California (SEAOSC) server. To
> *   subscribe (no fee) or UnSubscribe, please go to:
> *
> *   http://www.seaint.org/sealist1.asp
> *
> *   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you
> *   send to the list is public domain and may be re-posted
> *   without your permission. Make sure you visit our web
> *   site at: http://www.seaint.org
> ******* ****** ****** ****** ******* ****** ****** ********
>


******* ****** ******* ******** ******* ******* ******* ***
*   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
*
*   This email was sent to you via Structural Engineers
*   Association of Southern California (SEAOSC) server. To
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you
*   send to the list is public domain and may be re-posted
*   without your permission. Make sure you visit our web
*   site at: http://www.seaint.org
******* ****** ****** ****** ******* ****** ****** ********



******* ****** ******* ******** ******* ******* ******* ***
*   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
* 
*   This email was sent to you via Structural Engineers 
*   Association of Southern California (SEAOSC) server. To 
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you 
*   send to the list is public domain and may be re-posted 
*   without your permission. Make sure you visit our web 
*   site at: http://www.seaint.org 
******* ****** ****** ****** ******* ****** ****** ********