IBC seismic special inspection of wood lateral force resisting sy stems

[Subject Prev][Subject Next][Thread Prev][Thread Next]
Ladies:


I thought I would be politically correct since some people on the list have
been complaining.  IBC 1707.3 requires "periodic special inspection for
nailing, bolting, anchoring and other fastening of components within the
seismic force resisting system of wood buildings, including drag struts,
braces and hold-downs."  

The only exception is for R-3 occupancies per IBC 1704.   I have required
special inspection for structural wood lateral resisting systems for several
permits reviewed under the IBC code without complaint.  

Does the IBC only intend drag struts, braces and hold-downs with this
wording?  Should the periodic special inspection also include shearwall
nailing, floor nailing, roof nailing, anchor bolts, shearwall bottom plate
connections, shearwall top plate connections, ect...?



Thanks,

Scott M Haan P.E.
Plan Review Engineer
Building Safety Division 
Development Services Department
Municipality of Anchorage
http://www.muni.org/building
phone:907-343-8183  
fax:907-249-7399
mailto:haansm(--nospam--at)ci.anchorage.ak.us



******* ****** ******* ******** ******* ******* ******* ***
*   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
* 
*   This email was sent to you via Structural Engineers 
*   Association of Southern California (SEAOSC) server. To 
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you 
*   send to the list is public domain and may be re-posted 
*   without your permission. Make sure you visit our web 
*   site at: http://www.seaint.org 
******* ****** ****** ****** ******* ****** ****** ********