Just for your reference.
If you use the European Code (ENV 1991-1 Basis of
Design, Table 9.2),
you should use 0.9 as a load factor for the weight
of the foundation and 1.5 as a load
factor for the wind uplift.  Putting these
together you would have a "factor of safety" of
1.5/0.9 = 1.67.