I am designing a masonry building with a gable roof made up of cold form roof trusses. The roof pitch is 5/12 and roof deck acts as a diaphragm to distribute the loads to the end walls. The code is ASCE7-95.

I am concerned about the connectors between the truss and the wall. The truss mfr has submitted a load summary sheet from his in-house program which shows lateral loads as high as 1500lb from roof trusses. The trusses are classified as component and cladding.

I believe there should be no lateral loads if the truss is treated as a component. To obtain lateral load I claculated the pressures using MWRS. When wind is perpendicular there is suction on both sides (no net lateral pressure) and only 400lb lateral when wind is parallel.

I expalined this to the truss mfr but he claims that nobody has raised this issue before.

Also when I claculate the the net lateral from the roof and the walls do I evenly distribute that load to the connector at each end of truss.





_________________________________________________________________
Send and receive Hotmail on your mobile device: http://mobile.msn.com


******* ****** ******* ******** ******* ******* ******* ***
*   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
* * This email was sent to you via Structural Engineers * Association of Southern California (SEAOSC) server. To * subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
* Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you * send to the list is public domain and may be re-posted * without your permission. Make sure you visit our web * site at: http://www.seaint.org ******* ****** ****** ****** ******* ****** ****** ********