RE: Masonry Grout Admixture

[Subject Prev][Subject Next][Thread Prev][Thread Next]
Brent,
Why are they wanting to use a water reducer?  ASTM C476 forbids the use of
admixtures not specifically mentioned in the C476 or unless specified by the
purchaser.  On the other hand, water reducers can be beneficial in grout.
If used, I would require prism testing and/or a test panel.

Regards,
Harold O. Sprague

> -----Original Message-----
> From:	Brent Koch [SMTP:brent(--nospam--at)kochengineering.net]
> Sent:	Wednesday, October 30, 2002 11:55 AM
> To:	seaint(--nospam--at)seaint.org
> Subject:	Masonry Grout Admixture
> 
> I am reviewing a masonry grout mix design that incorporates a dose of a
> water reducing admixture (conforming to ASTM C494 Types A, B and D) and
> would appreciate any comments, opinions or reading reference from list
> members regarding the use of water reducing admixes in masonry grouts.
> 
> Brent R. Koch, P.E.
> Koch Engineering, Inc.
> 1962 Holmes Street
> Livermore, CA 94550
> tel:(925)456-7164
> fax:(925)456-7163 
> brent(--nospam--at)kochengineering.net
> 

******* ****** ******* ******** ******* ******* ******* ***
*   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
* 
*   This email was sent to you via Structural Engineers 
*   Association of Southern California (SEAOSC) server. To 
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you 
*   send to the list is public domain and may be re-posted 
*   without your permission. Make sure you visit our web 
*   site at: http://www.seaint.org 
******* ****** ****** ****** ******* ****** ****** ********