Anchorage of flexible diaphragms

[Subject Prev][Subject Next][Thread Prev][Thread Next]
Hello all,

Quick question regarding UBC Section 1633.2.8.1.  Item 5 requires that
wood elements of the wall anchorage system shall have a minimum actual
net thickness of 2 1/2".  If I have a condition where a wood plate is
installed atop a masonry wall and trusses sit atop that plate, does the
2 1/2" requirement apply to both the plate and the wood trusses (typical
pre-fab trusses are only 1 1/2" thick)?  What about a condition where
wood trusses might be supported by a ledger (directly bolted to the face
of the wall) and steel twist-straps are placed along the side of the
truss top chord back into the wall?

This has probably been asked before, so I'll probably check the archives
as well.