My personal rule of thumb is 30 ft between joints. I think MIA recommends
between 24 and 30 feet, but I haven't researched this issue in a while.

T. William (Bill) Allen, S.E. (CA #2607)	
ALLEN DESIGNS	
Consulting Structural Engineers	
http://www.AllenDesigns.com	
V (949) 248-8588	 .	 F (949) 209-2509	

-----Original Message-----
From: Mark D. Baker [mailto:shake4bake(--nospam--at)earthlink.net] 
Sent: Friday, March 04, 2005 10:50 AM
To: seaint
Subject: cmu wall control joints

For any cmu experts out there..

 

I have a 30'x30'x20' tall, 8" cmu building. I am thinking these dimensions
would be acceptable without any control joints in walls and would like some
other opinions.

 

Thanks,

 

Mark D. Baker

Baker Engineering

 


				
			 
	
		 
	
			 
 

 




******* ****** ******* ******** ******* ******* ******* ***