David,

"Collector elements, splices, and their connections to resisting elements shall have the design strength to resist the combined loads resulting from the special seismic load of section 1612.4"(UBC1633.2.6)
Do you think for collector themselves we should also include both 5%ECC  and omega factor?



Alex,PE




-----Original Message-----
From: David Topete [mailto:davetopete(--nospam--at)yahoo.com]
Sent: Thursday, March 24, 2005 10:02 AM
To: seaint(--nospam--at)seaint.org
Subject: Re: Collector Design with 5% ECC & omega


Collectors themselves, include 5%eccen.  Connections
of collectors to LFR elements, include the 5% eccen
AND Omega factor.  The 5% accidental is only if you
have a rigid diaphragm.
I'm sure someone will correct me if I'm wrong....  :-P
David Topete, SE
SF, CA
--- Alex <seaosd(--nospam--at)hotmail.com> wrote:
> do we have to include 5% ecc with omega factor for
> collector
> design?(UBC1633.2.6)


>


               
__________________________________
Do you Yahoo!?
Yahoo! Mail - Easier than ever with enhanced search. Learn more.
http://info.mail.yahoo.com/mail_250

******* ****** ******* ******** ******* ******* ******* ***
*   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
*
*   This email was sent to you via Structural Engineers
*   Association of Southern California (SEAOSC) server. To
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you
*   send to the list is public domain and may be re-posted
*   without your permission. Make sure you visit our web
*   site at: http://www.seaint.org
******* ****** ****** ****** ******* ****** ****** ********