RE: Stepping Basement Type Retaining Wall

[Subject Prev][Subject Next][Thread Prev][Thread Next]

We were advised by the geotech to use Geopiers at this site for cost efficiency. I don't want to introduce another foundations system unless I have to. Everyone is already complaining about having to use the Geopiers as it is. Even if it costs less to use the piles for the wall, I think it is going to be a big issue to introduce them now.

thanks,

Will


>From: "Sharon Robertson" <sharon(--nospam--at)arconengineers.com>
>Reply-To: <seaint(--nospam--at)seaint.org>
>To: <seaint(--nospam--at)seaint.org>
>Subject: RE: Stepping Basement Type Retaining Wall
>Date: Thu, 4 Aug 2005 11:06:45 -0700
>
>Will,
>
>Have you considered using soldier beams (piles) and spanning the wall
>horizontally?
>
>Sharon
>   -----Original Message-----
>   From: Will Haynes [mailto:gtg740p(--nospam--at)hotmail.com]
>   Sent: Thursday, August 04, 2005 10:48 AM
>   To: seaint(--nospam--at)seaint.org
>   Subject: Stepping Basement Type Retaining Wall
>
>
>   I have about a 15'-0" retaining wall that will also be serving as a
>basement wall along part of one side of the building. I have had this
>situation before and just used the second floor diaphragm to brace the wall
>at the top. But this wall is a lot higher, and the top of this wall varies.
>I need to use this wall as a shearwall also.
>
>   The floor framing will be composite steel beams. Has anbody had any
>success with designing the wall as a cantilever, letting it deflect, then
>attaching the framing after? I am afraid I am not going to properly predict
>the amount of deflection and end up with a problem. The geotech said the
>same.
>
>   Again, the top of wall will not be constant. It will be at the second
>floor height for about 20 ft, then gradually drop down to about 5'-0" tall
>along that side. So I know I will have to use a cantilever type of design at
>the areas where it is below second floor level. (I will have columns that
>will be supported on this wall from above where it is lower than second
>floor level).
>
>   I know I need to use a slotted connection at the steel to wall interface,
>to allow for adjustment for the deflection. But I am not sure how much of a
>slot to provide. The geotech guessed at about 4" of deflection at the top of
>the wall when it is at 15'-0" high. Any other suggestions to deal with this
>wall?
>
>
>
>   Will
>
>
>----------------------------------------------------------------------------
>--
>   Find e-mail and documents on your PC instantly with the new MSN Search
>Toolbar-FREE! ******* ****** ******* ******** ******* ******* ******* *** *
>Read list FAQ at: http://www.seaint.org/list_FAQ.asp * * This email was sent
>to you via Structural Engineers * Association of Southern California
>(SEAOSC) server. To * subscribe (no fee) or UnSubscribe, please go to: * *
>http://www.seaint.org/sealist1.asp * * Questions to seaint-ad(--nospam--at)seaint.org.
>Remember, any email you * send to the list is public domain and may be
>re-posted * without your permission. Make sure you visit our web * site at:
>http://www.seaint.org ******* ****** ****** ****** ******* ****** ******
>********


Find just what you're after with the new, more precise MSN Search - try it now! ******* ****** ******* ******** ******* ******* ******* *** * Read list FAQ at: http://www.seaint.org/list_FAQ.asp * * This email was sent to you via Structural Engineers * Association of Southern California (SEAOSC) server. To * subscribe (no fee) or UnSubscribe, please go to: * * http://www.seaint.org/sealist1.asp * * Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you * send to the list is public domain and may be re-posted * without your permission. Make sure you visit our web * site at: http://www.seaint.org ******* ****** ****** ****** ******* ****** ****** ********