RE: Metal Stud Track Gage

[Subject Prev][Subject Next][Thread Prev][Thread Next]
Another 2 cents to support your suggestion...

I typically spec an 18ga track for an 18ga stud wall
and 16 ga for 16ga and heavier wall studs, provided
there are no other loading concerns.  Deflection
tracks are often heavier than the wall studs.

Thicker tracks can be a bear for the finish details,
especially door and wind jambs.

For the rim joist, I would assume the same, but that's
more of a guess than a what-I've-done.  

Jim Wilson

--- Bruce Holcomb <bholcomb(--nospam--at)brpae.com> wrote:

> I haven't seen an answer to your question, so I'll
> throw in my 2 cents worth.  
> 
>  
> 
> Since the floor joists are bearing directly above
> the wall studs, there would be no vertical load to
> design to (well, technically, bearing... but that
> won't control).  The track needs to be thick enough
> such that the track flanges can resist the wall stud
> lateral end reaction.  SSMA has a design procedure
> on their website for deflection tracks, but I
> haven't seen anything for non-deflection conditions.
>  I believe the principles would still apply and you
> can perform a rational analysis... each track flange
> resists in cantilever bending ½ the wall stud
> lateral end reaction.  But, for most typical walls I
> design, I simply match the track thickness to the
> wall stud thickness and that is adequate.  
> 
>  
> 
> For the rim joist, I don't know of a minimum
> thickness.  You might want to consider evaluating
> the rim joist with the weigh of a man at mid-span...
> assuming someone stands right at the floor edge. 
> But then again, typical floor sheathing will be
> spanning perpendicular to the joists and will carry
> this load.
> 
>  
> 
>  
> 
> BDH
> 
>  
> 
> -----Original Message-----
> From: Rich Lewis
> [mailto:seaint03(--nospam--at)lewisengineering.com] 
> Sent: Monday, August 15, 2005 5:21 PM
> To: seaint(--nospam--at)seaint.org
> Subject: Metal Stud Track Gage
> 
>  
> 
> Are there rules of thumb, or maybe code requirements
> for the gage thickness of track for stud bearing
> wall?  Would the minimum track gage be a thickness
> or two lighter than the stud gage used in the wall? 
> I have a stud bearing wall supporting light gage
> metal floor joists.  The joists are aligned with the
> studs so technically there is not any weight
> supported by the track.
> 
>  
> 
> Similarly, the rim track/joist for the floor framing
> gage size.  I don't have a bearing wall above the
> joist framing so the rim joist only supports a
> non-bearing stud wall above.  The floor joists are
> 12 gage and extend out to the outside face so really
> there is no load on the rim joist.  Is there a
> minimum gage for the rim?
> 
>  
> 
> Thanks.
> 
>  
> 
> Rich
> 
>  
> 


******* ****** ******* ******** ******* ******* ******* ***
*   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
* 
*   This email was sent to you via Structural Engineers 
*   Association of Southern California (SEAOSC) server. To 
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you 
*   send to the list is public domain and may be re-posted 
*   without your permission. Make sure you visit our web 
*   site at: http://www.seaint.org 
******* ****** ****** ****** ******* ****** ****** ********