Re: 50' oc control joints for SOG ok?

[Subject Prev][Subject Next][Thread Prev][Thread Next]
Scott,
 
I would stay closer to 15 to 20 feet, and a 2:1 maximum aspect ratio for layout of control joints. Concrete cracks, and is hard to predict, the larger the area the greater the likelihood of cracking.  If its a warehouse, then I would look at spacing them further, I know there are other options out there. I have heard arguments to use Shrinkage compensating concrete.
 
Mike Cochran
 
 
In a message dated 8/16/2005 2:05:18 P.M. Pacific Standard Time, Scott.M.Haan(--nospam--at)poa02.usace.army.mil writes:

 

For a 6” slab on grade is it acceptable to have a 50’ oc control joint spacing for no. 4 @ 18” oc ea way.  I am looking at a tensile stress based on subgrade friction formula that calculates out.

 

Thanks.