No that's not correct, in an unreinforced wall the allow. flexural stress
in the block is lower for stack bond but in a reinforced wall they are the
same (stacked vs running) even partially grouted. Grouting the wall for all
intents and purposes increases you vertical load carrying ability not your
flexural capacity (unless you use a lot of flexural steel which in highly
loaded walls will increase the comp. stress block).

HTH,
Rand




                                                                           
             "Will Haynes"                                                 
             <gtg740p(--nospam--at)gmail.co                                             
             m>                                                         To 
                                       seaint <seaint(--nospam--at)seaint.org>          
             11/02/2006 06:25                                           cc 
             PM                                                            
                                                                   Subject 
                                       Stacked bond cmu                    
             Please respond to                                             
             <seaint(--nospam--at)seaint.or                                             
                    g>                                                     
                                                                           
                                                                           
                                                                           




I have not done much design with stacked block but I understand that it
should always be solid grouted when it is used to resist wind or for any
other structural purposes. Is this a code requirement? I think I remember
working on an addition to a school originally built in the 80's that had
existing stacked bond exterior walls that were reinforced horizontally and
vertically, but were only partially grouted.


Will Haynes


******* ****** ******* ******** ******* ******* ******* ***
*   Read list FAQ at: http://www.seaint.org/list_FAQ.asp
* 
*   This email was sent to you via Structural Engineers 
*   Association of Southern California (SEAOSC) server. To 
*   subscribe (no fee) or UnSubscribe, please go to:
*
*   http://www.seaint.org/sealist1.asp
*
*   Questions to seaint-ad(--nospam--at)seaint.org. Remember, any email you 
*   send to the list is public domain and may be re-posted 
*   without your permission. Make sure you visit our web 
*   site at: http://www.seaint.org 
******* ****** ****** ****** ******* ****** ****** ********