Bill,
 
The T.21-J compliance requirement appears to apply only to the in-plane seismically loaded piers.  By your email, this is not your case, so the strength-level capacity of the wall is 4,137lbs, while the allowable capacity is about 2,944 lbs (I don't know the M/Vd ratio).  Looks right to me.
 
V. Steve Gordin, SE
Irvine CA
----- Original Message -----
From: Bill Allen
Sent: Monday, July 02, 2007 14:19
Subject: Strength Design of Masonry Wall (per UBC)

I would like a confirmation that I’m looking at out of plane shear strength correctly.

 

Wall thickness = 8 in. (nominal)

Solid Grouted

F’m = 1,500 psi

b=12 in.

d=5.25 in.

Ae=91.2 in2 (from the equivalent solid thickness)

#6 bars at 8”

Temp. & Shrinkage horizontal steel

 

Mu/Vud >1, Cd=1.2, Vm(max)=63CdAe=63(1.2)(91.2)=6,895 lbs.

Vm=CdAe√F’m)=(1.2)(91.2)√(1,500)=4,239 lbs. < 6,895 lbs.

Vs = 0 since ρn = 0 (no shear reinforcement)

Vn = 4,239 lbs.

φv = 0.6

φv Vn = (0.6)(4,239) = 2,543 lbs.

 

Is this right?

 

If so, shear is limiting my design using strength design and it didn’t come anywhere close using working stress design.

 