Re: Hand rail Post -200 lbs lateral load Design

[Subject Prev][Subject Next][Thread Prev][Thread Next]
CBC 2007, also allows a 1/3 increase at ASD level. Try that.
 
Farzin S. Rahbar, SE
Vice President
David C. Weiss Structural Engineer & Associates, Inc.
(818) 227-8040 Ex. 13 Fax: (818) 227-8041


-----Original Message-----
From: h.d.richardson <h.d.richardson(--nospam--at)shaw.ca>
To: seaint(--nospam--at)seaint.org
Sent: Fri, Nov 19, 2010 9:14 am
Subject: Re: Hand rail Post -200 lbs lateral load Design

Dilip,
 
        You may be able to use a plastic analysis.  You would have a plastic hinge at the bottom of the post (in the insert?) and plastic hinges in the handrail at the top of the post and at the top of the adjacent posts.  I've been able to make this analysis work in the (dim and distant) past.
 
        Good luck.
 
Regards,
 
H. Daryl Richardson
----- Original Message -----
To: seaint
Sent: Thursday, November 18, 2010 3:46 PM
Subject: Hand rail Post -200 lbs lateral load Design

I need to check & approve a hand rail post with 200 lbs lateral load at top.
The post is 1-1/4" square x 11 ga with 1" x 8" long insert at bottom.(4" into square post)
The 1" solid round bar will be placed into 1-1/2" diameter x 4" deep drilled hole in concrete slab & filled with grout.
The 1-1/4" (ASTM A36) post works, however 1" diameter post do not considering the round bar will have maximum moment, just below the slab line.
Any practical way to design check this condition ?